Skip to content
    New: Medical Gas Outlet Retrofit & Rebuild Matrix — cross-reference legacy Chemetron, Ohio Diamond, Puritan-Bennett & more →
    ASSE Certified 24/7
    Medical Gas Service

    MTS Medical Gas Verification - Get a Quote on Verifications Here

    Medical Testing SolutionsJanuary 20, 20233 min read
    Share

    Medical gas verification is a critical safety process required by NFPA 99 for all new medical gas installations, renovations, and system modifications. An ASSE 6030 certified verifier must confirm that the system is safe for patient use before it goes live.

    What Is Medical Gas Verification?

    Medical gas verification involves a series of standardized tests and inspections that confirm the performance, reliability, and code compliance of medical gas systems, including oxygen, medical air, nitrous oxide, nitrogen, vacuum, and WAGD.

    Verification ensures that medical gas systems are installed correctly, minimizing the risk of gas leaks, cross-connections, contamination, and other hazards that could endanger patients.

    When Is Verification Required?

    Per NFPA 99 Section 5.1.14:

    • All new medical gas installations must be verified before use
    • Any system modification that breaches the pipeline requires verification downstream of the breach point
    • Additions of new outlets, zone valves, or alarm panels trigger verification requirements
    • Conversions from one gas to another require full verification

    What Tests Are Performed During Verification?

    An ASSE 6030 verifier performs the following tests per NFPA 99:

    1. Cross-connection testing, Verifies each outlet delivers only the correct gas, preventing potentially fatal cross-connections
    2. Oxygen concentration testing, Confirms oxygen purity meets USP standards (≥99%)
    3. Medical air testing, Tests for CO, CO₂, hydrocarbons, moisture, and particulates
    4. Pressure testing, Confirms system pressure meets specifications at all outlets
    5. Flow rate testing, Verifies adequate flow at each outlet under load
    6. Alarm verification, Tests master, area, and local alarm panels for correct operation and setpoints
    7. Zone valve testing, Confirms each zone valve shuts off only its designated area
    8. Gas purity analysis, Tests for contaminants including moisture and hydrocarbons

    NFPA 99 Code References

    Key NFPA 99 sections governing medical gas verification:

    • Section 5.1.12, Testing requirements (installer and verifier)
    • Section 5.1.14, Verification requirements and procedures
    • Section 5.1.14.5.6, Verification tests must be conducted after all installer tests are complete
    • Section 5.1.12.4.1.1, Any breach of the pipeline requires verification downstream
    • Section 5.1.12.4.1.3, Verification must be performed by ASSE 6030 qualified personnel

    Your Verification Preparation Checklist

    Before your verification appointment, ensure:

    • Blueprints for the new and existing system are available
    • A risk assessment meeting has been held with all department heads
    • Adequate backup gas supply is available (at least 2x estimated need)
    • Your backup supply has been verified and master alarms will function during shutdown
    • ASSE 6010 certified installers and ASME IX qualified brazers performed the work
    • The verifying company works independently (not for the contractor)
    • Project documentation will be complete and available

    Why Choose Medical Testing Solutions?

    Medical Testing Solutions is an ASSE 6030 licensed medical gas verification company providing NFPA 99 compliant certification services across all 50 states. Our verifiers are independent third parties, never affiliated with the installing contractor, ensuring unbiased results.

    All test instruments are calibrated per NIST (National Institute of Standards and Technology) requirements with documentation maintained on-site during all testing procedures.

    Call (754) 315-1078 or request a free quote.


    Related Resources

    This article is provided for educational purposes and reflects industry standards as of publication. Always verify against current NFPA 99, CGA, and AHJ requirements. Medical Testing Solutions is ASSE-certified and ready to help — contact us for facility-specific guidance.

    Request a quote for your facility

    Talk with Medical Testing Solutions about your next inspection, repair or equipment request.

    Get a quote in 1 business day

    I agree to receive text messages from Medical Testing Solutions, L.L.C. at the phone number provided, including informational and marketing messages. Consent is not a condition of purchase. Message frequency varies. Message & data rates may apply. Reply STOP to opt out or HELP for help. See our Privacy Policy and Messaging Terms.

    Prefer to talk? Call (754) 315-1078

    Related articles