NFPA 99 Compliant Signage
Customer Colors and Designs
Includes Zone Valve Designation Number
Includes Area/Master Alarm Electrical Circuit Number
NFPA 99 Compliant Signage
Customer Colors and Designs
Includes Zone Valve Designation Number
Includes Area/Master Alarm Electrical Circuit Number
5.1.11.2.1 Shutoff valves shall be identified with the following:
5.1.11.1.1 Piping shall be labeled by stenciling or adhesive markers that identify the patient medical gas, the support gas, or the vacuum system and include the following:
5.1.11.1.2 Pipe labels shall be located as follows:
5.1.11.4.1 Labeling of alarm panels for each indicator shall indicate the condition monitored and its area of surveillance. Area alarm panels shall be identified with the following:
5.1.3.1.8 Locations containing positive pressure gases other than oxygen and medical air shall have their door(s) labeled as follows:
Positive Pressure Gases
NO Smoking or Open Flame
Room May Have Insufficient Oxygen
Open Door and Allow Room to Ventilate Before Entering
5.1.3.1.9 Locations containing central supply systems or cylinders containing only oxygen or medical air shall have their door(s) labeled as follows:
Medical Gases
NO Smoking or Open Flame
5.1.11.2.3 Source valves shall be labeled in substance as follows:
SOURCE VALVE
FOR THE (SOURCE NAME).
5.1.11.2.4 Main line valves shall be labeled in substance as follows:
MAIN LINE VALVE FOR THE (GAS/VACUUM NAME)
SERVING (NAME OF THE BUILDING).
5.1.11.2.5 The riser valve(s) shall be labeled in substance as follows:
RISER FOR THE (GAS/VACUUM NAME) SERVING
(NAME OF THE AREA/BUILDING SERVED BY THE
PARTICULAR RISER).
5.1.11.2.6 The service valve(s) shall be labeled in substance as follows:
SERVICE VALVE FOR THE (GAS/VACUUM NAME)
SERVING (NAME OF THE AREA/BUILDING
SERVED BY THE PARTICULAR VALVE).
5.1.11.2.7 Zone valve box assemblies shall be labeled with the rooms, areas, or spaces that they control as follows:
ZONE VALVES FOR THE (GAS/VACUUM NAME)
SERVING (NAME OF ROOMS OR SPACES SERVED
BY THE PARTICULAR VALVE)
Labeling shall either be visible from outside the zone valve box assembly through the cover or be replicated on the outside, but not affixed to the removable cover
MTS is an ASSE 6030© Licensed medical gas verification company and providing NFPA code compliant medical gas certification services all across the U.S.
MTS is an ASSE 6020© Licensed medical gas inspection service company, providing annual inspections on medical gas systems throughout the U.S.
MTS provides medical gas systems installations per the NFPA 99 using our certified ASSE 6010© Licensed medical gas plumbers all across the U.S.
MTS is an ASSE 6040© Licensed medical gas maintenance company providing the highest quality medical gas maintenance services all across the U.S.