card-img

Description

SRD-C3U2-BM – Suction Regulator – Digital, Continuous 3 mode, USA, 1/8″ FNPT, British. Suction Regulators, Suction Regulators – Digital, Continuous 3 Mode, F2, USA, Amico, Amico Suction Regulator – Digital, Continuous 3 mode, USA, 1/8″ FNPT, British, SRD-C3U2-BM.

Specification Sheet

sot_sp_vac_reg

Frequently Asked Questions

Yes, MTS has various partnerships with a number of medical gas installation contractors. Each sub contractor employees qualifying ASSE 6010 Medical Gas Installers ready to meet your needs.
A Medical Gas Certification (Also called a medical gas verification) is an NFPA required inspection and approval of newly installed medical gas delivery systems. All newly in installed medical gas pipeline and equipment must be certified by an ASSE 6030 before use.
Answer: Per NFPA guidelines, it is a requirement for any facilities using medical grade gases for the purpose of human consumption to have their gas delivery systems inspected by and ASSE 6040. Read more about Medical Gas Inspections Here.
Answer: Yes, MTS provides annual medical gas inspections. We provide discounts on Annual Inspections when you sign multi year contracts. Read more about Medical Gas Inspections Here.
Answer: The Plumbing and Mechanical Systems Board issues medical gas piping certification to medical gas system installers who possess valid certification from the National Inspection Testing Certification Corporation or NITC. Certification from other organizations may be considered with approval of the board.
Yes, we can adapt any fittings to the desired hosing for any medical grade gas. High pressure gases such as Nitrogen can also be accommodated.
Yes, Those items for shipment to countries outside of the U.S. may be subject to taxes, customs duties and fees levied by the destination country (“Import Fees”). The recipient of the shipment is the importer of record in the destination country and is responsible for all Import Fees.
With respect to each item for which Import Fees have been calculated, you authorize Export or Merchant (as applicable) to designate a carrier (“Designated Carrier”) to act as your agent with the relevant customs and tax authorities in the destination country, to clear your merchandise, process and remit your actual Import Fees for such item.
Import Fees Deposit” represents an estimate of the Import Fees that will be levied on the items in your order for shipment to countries outside of the U.S. By placing your order, you agree to allow Export and/or Merchant (as applicable) to collect the Import Fees Deposit for the applicable items in your order. This deposit will be used, on your behalf, to reimburse the Designated Carriers for the import fees that they have paid on your behalf to the appropriate authorities of the destination country.
Answer: Per NFPA guidelines, it is a requirement for any facilities using medical grade gases for the purpose of human consumption to have their gas delivery systems inspected by and ASSE 6040. Read more about Medical Gas Inspections Here.

Vacuum Pumps
And Compressors

Medical Gas Services

Verifications

MTS is an ASSE 6030© Licensed medical gas verification company and providing NFPA code compliant medical gas certification services all across the U.S.

Read More

Inspections

MTS is an ASSE 6020© Licensed medical gas inspection service company, providing annual inspections on medical gas systems throughout the U.S.

Read More

Installations

MTS provides medical gas systems installations per the NFPA 99  using our certified ASSE 6010© Licensed medical gas plumbers all across the U.S.

Read More

Maintenance

MTS is an ASSE 6040© Licensed medical gas maintenance company providing the highest quality medical gas maintenance services all across the U.S.

Read More

Terms and Conditions Cookie Policy Privacy Policy